SBFS042 June 2020 AFE3010
PRODUCTION DATA.
Figure 15 is the typical application for the AFE3010 when the SEL pin is grounded. The system requirements shown in Table 4 are based upon the UL-943 standard. The required component power and voltage ratings should be chosen based upon the line voltage. See Table 5 for more information on power ratings.
DESIGN PARAMETER | VALUE |
---|---|
Line or source voltage | 120 VAC (±15%) |
Line frequency | 50-60 Hz |
Line polarity (connection to GFCI unit) | Normal and reverse polarity |
Operational temperature | –40 °C to +105 °C |
Rated load | 20 A RMS |
Ground fault threshold (trip point) | 5 mA RMS |
Ground fault threshold variation over all parameters | ±0.5 mA RMS |
Neutral-to-ground fault detection | Per UL-943 |