Each high-side driver has a dedicated PWM generator with 10-bit duty cycle resolution. The frequency and duty of each PWM generator can be controlled independently.
When configuring the high-side driver for operation with internal PWM generator, the frequency must be selected before configuring the high-side driver with internal PWM generator.
Required Register Configuration Sequence:
The frequency of the PWM generator is controlled by bits PWM_OUTX_FREQ from register HS_PWM_FREQ_CNFG as shown in the table below:
PWM_OUTX_FREQ | PWM Frequency (Hz) |
---|---|
00b | 108 |
01b | 217 |
10b | 289 |
11b | Reserved |