The VOUT_UV_FAULT_RESPONSE instructs the device on what action to take in response to an output undervoltage fault.
Upon triggering the undervoltage fault, the following actions are taken:
The VOUT_UV_FAULT_RESPONSE command must be accessed through Read Byte/Write Byte transactions.
The VOUT_UV_FAULT_RESPONSE command is shared between Channel A and Channel B. All transactions to this command will affect both channels regardless of the PAGE command.
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
RW | RW | RW | RW | RW | RW | RW | RW |
VO_UV_RESP |
LEGEND: R/W = Read/Write; R = Read only |
Bit | Field | Type | Reset | Description |
---|---|---|---|---|
7:0 | VO_UV_RESP | RW | NVM |
00h: Ignore. The controller will set the appropriate status bits, and alert the host, but continue converting power. BAh: Shutdown and restart. The controller will shutdown the channel on which the fault occurred, and attempt to restart 20ms later. This will occur continuously until the condition causing the fault has disappeared, or the controller has been disabled. 80h: Latch-off and do not restart. To clear a shutdown event due to a fault event, the user must toggle the AVR_EN/BEN pin and/or the ON bit in OPERATION, per the settings in ON_OFF_CONFIG, or power cycle the bias power to the V3P3 pin of the controller device. |