GPI Fault Enable must be set to enable this feature. When set, if there is no fault on a Fault Bus, the Fault Pin is digital input pin and listen to the Fault Bus. When one or multiple UCD90160A devices detect a rail fault (see Table 7-7), the corresponding Fault Pin is turned into active driven low state, pulling down the Fault Bus and informing all other UCD90160A devices of the corresponding fault. This way, a coordinated action can be taken across multiple devices. After the fault is cleared, the state of the Fault Pin is turned back to an input pin.
Events | Description |
---|---|
RESEQUENCE_ERROR | Rail fails to resequence |
SEQ_ON_TIMEOUT | Rail fails to meeting sequence on dependency in predefined period |
SEQ_OFF_TIMEOUT | Rail fails to meeting sequence on dependency in predefined period |
OT_FAULT | Temperature Rail has over temperature |
IOUT_UC_FAULT | Current Rail is below UC threshold |
IOUT_OC_FAULT | Current Rail is over OC threshold |
VOUT_UV_FAULT | Voltage Rail is under UV threshold |
VOUT_OV_FAULT | Voltage Rail is over OV threshold |
TON_MAX_FAULT | Voltage rail fails to reach power good threshold in predefined period. |