SLLU364 may 2023 MCT8315A
This fault gets triggered when the phase current is below No motor lock threshold % of base current.
Step 1: Make sure the motor phases are connected to J8.
Step 2: If the fault persists, set the No-Motor lock current threshold [NO_MTR_THR] to 0.005 V.
Step 3: For low inductance motors, increase PWM switching frequency [PWM_FREQ_OUT].
Step 4: Increase Min duty cycle [MIN_DUTY] during closed loop operation.
Please note that device might trigger Loss of sync [LOSS_OF_SYNC] when motor phases are disconnected while the motor is spinning.