TIDUEZ8C december 2022 – june 2023
In an unearthed power distribution system, the isolation barrier protects the user and components sitting on the low-voltage side by preventing high currents flowing to protective earth. The isolation barrier is expected to be of a resistive nature. Nevertheless, some factors such as improper earth connection or humidity can increase the isolation capacitance to earth of the system.
In this system, under proper operation or asymmetrical fault of the isolation barrier, this static capacitance to earth forces a delay in the settling time of the isolation voltage when the resistive branch is switched in. A period of wait time must occur after the resistive branch is switched in and before the measurement of the insulation voltage is done. This reduces overall measurement speed in systems with higher insulation capacitance. The time constant of the resulting RC circuit is shown in Equation 15, assuming RisoN is small and RisoP is high.
As an example, in case of a insulation capacitance of 10 nF and a RstP of 68.1 kΩ, as observed on the 400-V version of this design, and RisoP of 10 MΩ, a time constant of 676 µs is the result. A delay between the closing of the switch and the start of the measurement of at least 3 τ is recommended to let the voltage settle to 95% of the final value.
By allowing higher currents across the isolation barrier through the switched-in resistive branch, faster settling times can be achieved. The current through the switched-in branch Ist can be calculated using Equation 15
Hence, consider the tradeoff between faster settling times and power dissipation when designing a resistive divider branch, while keeping the maximum allowed current in mind. Further details on the implementation in this reference design are found in Section 2.3.