The TIDA-020065 software implements 4 different fuse channels. Table 3-4 shows the time-current characteristics of these channels.
CHANNEL NUMBER | INOM (A) | I2t (A2s) | COOLDOWN AFTER FUSE SHUTDOWN (s) | SOFTWARE CURRENT LIMIT (A) | PULSE WIDTH FOR FIXED-DELAY SHUTDOWN (ms) | COOLDOWN AFTER FIXED-DELAY SHUTDOWN (s) |
---|---|---|---|---|---|---|
1 | 15 | 340 | 4 | 65.5 | 4 | 4 |
2 | 20 | 520 | 4 | 65.5 | 4 | 4 |
3 | 25 | 1000 | 4 | 65.5 | 4 | 4 |
4 | 30 | 1500 | 4 | 65.5 | 4 | 4 |
For all channels, the immediate shutdown threshold is fixed by hardware components at 100A. The TPS1213-Q1 is configured for latch-off and fastest shutdown during SC events (< 6μs).