This reference design detects mA-level AC and DC ground fault currents. An auto-oscillation circuit is implemented using a DRV8220 H-bridge that drives the magnetic core in and out of saturation. In addition, an active filter circuit is implemented to identify fault current signal and level.
Features
- Discrete AC and DC ground fault detection circuit
- Designed to sense fault current thresholds of 6-mA DC, 30-mARMS AC based on IEC62752 and IEC62955
- Detection-to-response time < 25 ms (not including relay delay time)
- Adjustable AC and DC trip thresholds via software