Usage of the Average Current Sensor

The current monitor (IMONLIM) function can be enabled when operating power stages in parallel and being used in multiple options. So with two power stages following options can be possible:

  • none used - both disabled
  • only one used as current monitor, second is disabled
  • first current monitor used for input current sensing, second used for output current sensing

In Figure 3-1, a configuration with the current monitor on the input and the current monitor on the output is shown.