SPRACO3 October 2019 INA240 , LMG5200 , TMS320F280021 , TMS320F280021-Q1 , TMS320F280023 , TMS320F280023-Q1 , TMS320F280023C , TMS320F280025 , TMS320F280025-Q1 , TMS320F280025C , TMS320F280025C-Q1 , TMS320F280040-Q1 , TMS320F280040C-Q1 , TMS320F280041 , TMS320F280041-Q1 , TMS320F280041C , TMS320F280041C-Q1 , TMS320F280045 , TMS320F280048-Q1 , TMS320F280048C-Q1 , TMS320F280049 , TMS320F280049-Q1 , TMS320F280049C , TMS320F280049C-Q1 , TMS320F28374D , TMS320F28374S , TMS320F28375D , TMS320F28375S , TMS320F28375S-Q1 , TMS320F28376D , TMS320F28376S , TMS320F28377D , TMS320F28377D-EP , TMS320F28377D-Q1 , TMS320F28377S , TMS320F28377S-Q1 , TMS320F28378D , TMS320F28378S , TMS320F28379D , TMS320F28379D-Q1 , TMS320F28379S
After verifying the space vector generation and PWM modules, the 3-phase inverter hardware can be tested by looking at inverter outputs U, V, and W on a scope. This can be compared against the PWM pulses fed into the inverter. It is advisable to gradually increase the DC bus voltage or change 'VdTesting' and 'VqTesting' values during this test. Check inverter outputs U, V, and W using an oscilloscope with respect to the inverter GND, while taking care of scope isolation requirements. This ensures that the inverter is working properly.
CAUTION
After verifying this, take the controller out of real time mode (disable), reset the processor. Note that after each test, this step needs to be repeated for safety purposes, otherwise an improper shutdown might halt the PWMs at certain states where the inverter can draw currents high enough to damage itself. Hence caution needs to be taken while doing these experiments.