TIDUEZ0A March 2021 – March 2022 TMS320F28P550SJ , TMS320F28P559SJ-Q1
Close loop test output waveforms in Figure 3-6 show clean sinusoidal waveforms at the nominal load. During the experiments, no important zero crossing distortion was observed in the currents. Total harmonic distortion less than 4% was measured.
Table 3-1 and Table 3-2 collect the efficiencies of the PFC at 230 VRMS, respectively for two different DC bus voltages: 600 V and 800 V. The results obtained from the power analyzer are taken from 2 kW to 11 kW. In most of all the operating points, the power efficiency is higher than 98% by reaching a maximum of 98.62%.
DC BUS VOLTAGE (V) | AC GRID CURRENT (A) | INPUT POWER (W) | OUTPUT POWER (W) | EFFICIENCY |
---|---|---|---|---|
605.3 |
3 |
2045.7 |
1980.2 |
96.8 |
605.34 |
5.22 |
3559.5 |
3506.1 |
98.5 |
605.38 |
7 |
4773.3 |
4707.4 |
98.62 |
605.2 |
8.9 |
6068.9 |
5978.5 |
98.51 |
605.28 |
10.9 |
7432.7 |
7309.3 |
98.34 |
605.34 |
13.05 |
8898.8 |
8731.5 |
98.12 |
605.5 |
15.2 |
10364.9 |
10148.3 |
97.91 |
605.8 |
16.5 |
11251.4 |
11006.1 |
97.82 |
DC BUS VOLTAGE (V) | AC GRID CURRENT (A) | INPUT POWER (W) | OUTPUT POWER (W) | EFFICIENCY |
---|---|---|---|---|
803.4 |
3.02 |
2070 |
1976.8 |
95.5 |
801.4 |
5.24 |
3601.8 |
3511.8 |
97.5 |
802.4 |
7.01 |
4830 |
4747.9 |
98.3 |
803.4 |
8.95 |
6141 |
6042.7 |
98.4 |
803.5 |
10.93 |
7521 |
7408.2 |
98.5 |
802.8 |
12.98 |
8970 |
8826.5 |
98.4 |
803.8 |
15.21 |
10488 |
10304.5 |
98.25 |
803.1 |
16.52 |
11385 |
11180.1 |
98.2 |
All the data summarized in the tables have been collected and plotted as shown in Figure 3-7. At low power it is better to keep the PFC to work at lower DC bus voltage. Conversely, at a higher current keeping higher DC bus voltage leads an important efficiency improvement of 0.4%.
The final design dimensions are outlined in Table 3-3 and show a total volume of 4.3 L. With a power rating of 11 kW, this results in a power density of 2.57 kW/L.
AXIS | DIMENSION |
---|---|
X | 300 mm |
Y | 220 mm |
Z | 65 mm |
Volume | 4.29 liters |