SLUA560D June 2011 – March 2022 UCC28950 , UCC28950-Q1 , UCC28951 , UCC28951-Q1
The PSFB uses a transformer to deliver energy from the primary to the secondary. The voltage is stepped up or down through the transformers turns ratio (a1).
Estimated FET voltage drop (VRDSON):
Select transformer turns based on 70% duty cycle (DMAX) at minimum specified input voltage. This will give some room for dropout if a PFC front end is used.
Calculated typical duty cycle (DTYP) based on average input voltage.
To keep the RMS current in the output capacitance to a minimum LOUT will be selected so the inductor ripple current (ΔILOUT) will be 20% of the DC output current. ΔILOUT is needed to calculate transformer peak and RMS currents
Care needs to be taken in selecting a transformer with the correct amount of magnetizing inductance (LMAG). The following equations calculate the minimum magnetizing inductance of the primary of the transformer (T1) to ensure the converter operates in peak-current mode control. If LMAG is too small the magnetizing current could cause the converter to operate in voltage mode control instead of peak-current mode control. This is because the magnetizing current is too large, it will act as a PWM ramp swamping out the current sense signal across RS.
Figure 4-1 shows T1 primary current (IPRIMARY) and synchronous rectifiers currents, (QE (IQE) and QF (IQF)), with respect to the synchronous rectifier gate drive currents. Note that IQE and IQF are also T1’s secondary winding currents as well. Variable D is the converters duty cycle.
Calculate T1 secondary RMS current (ISRMS):
Secondary RMS current (ISRMS1) when energy is being delivered to the secondary:
Secondary RMS current (ISRMS2) when current is circulating through the transformer when QE and QF are both on.
Secondary RMS current (ISRMS3) caused by the negative current in the opposing winding during freewheeling period, please refer to Figure 4-1.
Total secondary RMS current (ISRMS):
Calculate T1 Primary RMS Current (IPRMS):
T1 Primary RMS (IPRMS1) current when energy is being delivered to the secondary.
T1 Primary RMS (IPRMS2) current when the converter is free wheeling.
Total T1 primary RMS current (IPRMS)
The transformer calculations were given to Vitec a magnetic manufacturer to design a custom transformer to meet our design requirements. The transformer they designed for this application is part number 75PR8107 and the transformer has the following specifications.
Measured leakage inductance on the Primary:
Transformer Primary DC resistance:
Transformer Secondary DC resistance:
Estimated transform losses (PT1) are twice the copper loss.
This is just an estimate and the total losses can vary based on magnetic design.
Calculate remaining power budget: